    Irio serial start menu

    Voici une procédure fournie par Global-na-tech afin de tenter de ré-initialiser la config IP d'un iRIO à travers une liaison série.

    iRIO start process break to be able to activate DHCP mode or to change Network settings (IP address, gateway, mask)

    Use Hyperterminal Windows communication accessory: 115200bps, no parity, 1 stop, no flow control.

    A serial RS232 is required on the PC (or a USB-RS232 interface)

    When iRIO is powered on, the following text appears after about 30 seconds:

    MAC : 00:B0:CE:00:49:90
    IP Address : 10.199.179.54
    IP Gateway : 10.199.179.1
    Network Mask : 255.255.255.0
    IP Primary DNS : 10.199.179.33

    Serial Number : 12230043

    StartX Version : 4.0.11.0
    Xflow Version : 3.3.1.0
    OS Version : Windows CE.net Version 4.20.0000
    Build Version : BSP : 1.7 PRJ : 1.0
    uMon Version : Version 2.4
    Build Version : Nov_08,2011 16:47:00
    Manufacturer : B2i Electronics
    Xflow starts : 28
    Last start : 09/01/2013 17:38:51
    Last reset : 12/12/2012 17:30:28

    Last control : 18/07/2012 11:04:08
    Connexium status : no
    Pervasive status : registered

    Press any key to enter command line mode !
    2

    You have 3 seconds to press a key in order to stop the iRIO starting process.

    Code Then you are in the command line mode and the following menu is displayed:
    <1> TeleBoot
    <2> Xflow
    <3> Display system informations
    <4> Modify system parameter
    <5> Reboot the System
    <6> Discard xflow.wst (xflow starts without configuration)
    <Esc> To exit…

    You have 10 seconds to make your choice.

    If you want to reset configuration press the ”6” key (Discard xflow.wst)

    At every stage of this process, if you don’t press a key in the given time, the iRIO will continue with its starting process and finally launch Xflow (1 second blink on the green led indicator). If you want to recover this starting process, you have to reset the iRIO or switch off its power supply again.